r/SteamHeat • • 4h ago

Bleeding baseboard heaters

Thumbnail gallery
1 Upvotes

r/SteamHeat • • 23h ago

Auto feed kicks on while heat is on

5 Upvotes

I’m certainly no professional, but I consider myself pretty handy and knowledgeable.

With that said, I don’t mess with my boiler but I feel like something is going very wrong.

I can hear my water autofeed turn on when my heat is actively kicked on. So the boiler is refilling when most of the water is in the form of steam throughout all the radiators. So when it cools back down, I assume the boiler is now overfilled. Is this an accurate assumption?

I hear the autofeed kick on pretty much daily. The spyglass is always full even when I drain water so I assume there’s sediment in there preventing the water to drain out.

I want to call someone to look at it but I don’t want to if it’s literally nothing and this is normal (besides the spyglass being full). I grew up with forced heat so this is all new to me.

We had someone working on it towards the end of winter last year so it didn’t get much use after the work was done so I don’t know if this is how it’s supposed to be.


r/SteamHeat • • 1d ago

New radiator connection

Thumbnail
gallery
5 Upvotes

I need some advice on the best way to connect this radiator. Valve is 2” and new to me rad is 1 1/2”. The radiators connection is about 2” higher than my valve.
Should I try to remove the valve and extend it up? Does the union (compression) nut on the radiator need to go directly into the valve or could I use some fittings/reducer to get thing connected?


r/SteamHeat • • 1d ago

Need new steam boiler

Thumbnail gallery
2 Upvotes

r/SteamHeat • • 2d ago

My little world.....

Post image
14 Upvotes

r/SteamHeat • • 3d ago

Water is clean but seems a bit low

Post image
1 Upvotes

Had a really nice steam knowledgeable guy drive a few hours to come look at my system since there seems to be no one in my area that understands or cares enough to understand.

He marked that level on there as to where it roughly should be. Pay no mind to the gauge. It's broken and tells me the system is running at 10-20psi at rest. Water level doesn't get up much further than that. Surges a little while running but not inches; maybe 1/2 inch.

Guys here the other day restored a capped off vent but didn't redo the elbow so the vent was pointing at an angle and just vented steam into the basement. That was recapped. There was also a small leak at a union which they tightened up and think they fixed. We'll see.

Should I add water to this or leave it be if things are working? It has an automatic water feeder.


r/SteamHeat • • 3d ago

Low Water - Again

Post image
2 Upvotes

As seen in the pic, the water level was very low, causing the boiler to turn off. And there is some black junk in there.

Not sure why it keeps getting so low. This happened a couple times last winter and I had to manually feed water to keep it going. I also have the automatic feed turned up to 3 gallons per fill, with the maximum delay time. That seemed to fix the problem last winter. In the past, there was not all this black crud inside the glass.

This time I manually fed 10 gallons back into it, and the boiler is working.

There is no leaking water anywhere, not at the boiler or the radiators. And I don't see steam coming out of the chimney when the boiler is running.

Previously (last year) the system was venting a lot of steam from the hot water return lines, but that is not happening anymore since I replaced one of the relief valves that seemed to have had failed.

The boiler is a Weil-Mclain P-SGO-03 series 3 oil-fired steam boiler. The water feeder is Saf-Gard model VXT-120 and the low water cutoff is Saf-Gard 450.

Maybe there is a water leak inside the boiler? I don't know where else the water would be going. This doesn't happen all the time, just intermittently & especially in cold weather.

And I'm not sure if the water feeder just didn't activate this time, maybe it is not connected properly to the LWCO? The LWCO was showing the amber light, so it did know that the water level was low. And the water feeder seems to be working.

The oil company performed the annual tune-up on the boiler in July and everything seemed fine at that time. Should I just have them come back & clean it out again?


r/SteamHeat • • 4d ago

Main vent stuck

Post image
4 Upvotes

Following up on an earlier conversation and after my plumber went non-responsive, I attempted to replace my main vent myself but I can’t get the old one off. I try pulling the wrench towards me on that picture and I added pliers below to keep the other part secured but it does not budge. Can I use a rubber mullet to get some extra force on the wrench? Any other tips? I don’t want to end up with a broken pipe. Being in a tight space doesn’t make it easier. Thanks!


r/SteamHeat • • 5d ago

Snapping Noise

Post image
3 Upvotes

Sorry if this has been asked before but I checked around and could not find any answers. I am new to steam heat and had some pipes replaced this spring and this doohickey (technical term) was added. It makes a snapping noise every few minutes when the heat first comes on and then slowly stops. Any problem with that? Should I sleep outside tonight?


r/SteamHeat • • 5d ago

Snapping Noise

Post image
3 Upvotes

Sorry if this has been asked before but I checked around and could not find any answers. I am new to steam heat and had some pipes replaced this spring and this doohickey (technical term) was added. It makes a snapping noise every few minutes when the heat first comes on and then slowly stops. Any problem with that? Should I sleep outside tonight?


r/SteamHeat • • 5d ago

painted over air valve

Thumbnail
gallery
3 Upvotes

hi everyone,

i recently moved into a new apartment and the "hot pipe" in our bathroom doesn't get hot when the other radiators are on. the air valve is completely painted over so i'm guessing that no air can escape which keeps the steam from entering the pipe. i thought it was a regular bullet-style valve with a pinhole at the top, but upon further inspection, the top part looks way thicker than what i'm used to.

i was going to just poke a hole through the top with a nail, but the paint is too thick and i'm not even sure where the opening is on this one. any advice?


r/SteamHeat • • 6d ago

Boiler Heating But Not Radiators

2 Upvotes

I turned the system off at the thermostat the other day to change an air vent on one of my radiators (didn’t end up happening, long story. Anyway, I turned the system back on, and nothing. No boiler, no heat.

So, I know the system leaks, so I go down and check the sight glass. Sure enough, it’s empty. So, I start filling it. Nothing, nothing, nothing, then suddenly, water comes out of the boiler overflow. Now I’m right here, so I shut it of immediately. What do you know? The boiler kicks on (still nothing in the sight glass, but thats not my problem rn, there’s water in the boiler and it’s running, we should be good).

Only we’re not. The boiler is getting warm (the basement is downright hot) and the pipes in the basement are all hot. But none of the radiators are heating up. Not the inlet pipes, nothing. Only the pipes in the basement are getting hot. Anyone have any ideas as to what might cause this (and how to fix it?)


r/SteamHeat • • 6d ago

Leaky radiator help needed

2 Upvotes

Is a steam-heat radiator more likely to leak when the valve is fully open or fully closed? Or does it not matter? Mine was leaking so I replaced the vent, which helped but it's still leaking a little.  I don't want my floors to be damaged.

Currently the valve is fully closed. Thanks in advance for any wisdom.


r/SteamHeat • • 6d ago

Value of replacing?

Post image
4 Upvotes

How much more efficient is a new boiler vs this 1987 model?


r/SteamHeat • • 7d ago

Leaking fitting

2 Upvotes

I have a tee that is leaking due to a crack in the fitting. It looks like a previous epoxy repair has failed. I would have to undo quite a bit of piping to replace it. My question is, can I weld the crack?


r/SteamHeat • • 7d ago

Air valve and brass plug.

Thumbnail gallery
2 Upvotes

r/SteamHeat • • 8d ago

Old converted burner aquastat assistance

Thumbnail gallery
1 Upvotes

r/SteamHeat • • 9d ago

Something Isn't Right

2 Upvotes

I'm living in a house with steam heat. The rest of the house is working well, but the radiator in my bedroom (the only one I really care about) is giving me issues.

When I first turned the system on this season, my radiator wasn't heating at all. I discovered the air vent was all the way closed. I opened it and it started heating, however pretty quickly it started banging, and blowing a lot of air, and eventually a bit of hot water out of the top of it.

Some googling says that either the air vent is going bad, or there is water staying in the radiator. The first suggestion I always get is to check if the service valve is partially closed, as this can cause water to stay in the radiator. I tried this, but the valve is stuck. Won't turn either way, at all. Should I keep messing with this valve, or just ignore it, assume it is all the way open (I am getting heat), and replace the air vent?

I can take an air vent off of one of the other radiators (there are a couple rooms that are completely shut off, or can be completely shut off), however I don't really want to swap it just to wear out another valve in a week if it is more likely another underlying problem. Also I don't want to just go willy nilly screwing and unscrewing things without first consulting the "experts" as this is my first even encounter with steam heat.

Any advice is greatly appreciated, please let me know if you have any questions or need any clarification. Thank you all in advance!


r/SteamHeat • • 9d ago

Radiator valve stuck

5 Upvotes

Trying to open the valve on my radiator but it seems like the black plastic is just spinning in place? Any recommendations?


r/SteamHeat • • 10d ago

Surging issue, think i know the problem but need guidance

Post image
5 Upvotes

I had a new boiler utica peg112 put in and it has a surging problem which makes it cuts on and off every 30/45 secs. I have been researching and every where pointed me to check the near boiler piping. I measured everything out and all above the min spec and then i noticed the installer used the set up for a two supply tappings instead of the one. While waiting for him to get back to me, i was thinking a solution could be to cut where the green line is and put a cap on it and cap the unused outlet. Would this be acceptable?


r/SteamHeat • • 10d ago

Pressuretrol set way too high

7 Upvotes

We just purchased a 1905 home with one pipe steam radiators. I have no experience with these and unfortunately they’re not very common in the Knoxville, TN area. The one HVAC company that even said they work on these came to look at it and didn’t even know one pipe steam was a thing, didn’t really do anything, and took $100 and said everything looks good.

Anyway, I started reading and noticed that the Honeywell P404 additive pressuretrol has its cut in set to 8 PSI. I’ve watched the boiler 0-30 psi gauge and it just stays at 1-1.5psi while running (1psi when off too). Is this something I can just adjust myself? Don’t want to break this thing and then not be able to hire someone to fix it


r/SteamHeat • • 11d ago

Can I fix this myself? My maintenance has been out 3 times now and has STILL not fixed the leaks on my radiator. They were just out here today and the leak keeps getting worse every time they work on it.

14 Upvotes

I moved into my apartment in September before the heat was on. Didn’t have any issues in here before the boilers started for the season. As soon as the heat kicked in every radiator had an issue with leaks or clogs.

I’ve had to put in multiple requests and do multiple follow up calls for someone to even come out for the first leak (and leaks on my other two radiators). He came out last weekend to fix the leak on this one which originally was leaking from the gasket on the valve and he replaced the entire valve pipe. It started leaking in a new spot.

Put in a new request and have told the property company it’s damaging the floors or I’ve had to turn off the heat to stop it. They had no urgency despite me saying I had the heat turned off to contain the leak in freezing temps.

Called again today and they sent out maintenance again. He put more sealant on the middle part of the valve and now there’s water squirting out all around the supply valve and getting in the floors. I don’t know how else to explain to them what’s going on to get it fixed and don’t want to be charged at the end of my lease for this water damage. I can’t go without heat any longer by turning it off because it’s too cold. Can I somehow fix this myself since the property company keeps sending out the same guy who isn’t fixing it properly???


r/SteamHeat • • 11d ago

Normal water level during operation?

Post image
3 Upvotes

Cleaned sight glass last week and flushed out low water cutoff. This morning the water level was between 1/2 and 3/4 of the sight glass, went to check just now (5pm) after a few hours of heating and it was down to this level. Is this normal variation and the condensate is just taking a bit of time to return? Or cause for concern?

Update: water returns to normal level when boiler is off, which luckily means no leaks to the system. Guess this is just condensate slow to return to boiler? Our radiators are on the third floor so it's possible, hopefully not a wet return issue.