A simple example for discussion: a 20 kWh battery supplying a steady 5 kW load gives four hours on paper. But that assumes all 20 kWh is available to the load.
If the usable discharge window is 90% of nominal capacity and the conversion efficiency is 94%, the simplified estimate becomes:
20 kWh × 0.90 × 0.94 ÷ 5 kW ≈ 3.4 hours
Those percentages are hypothetical, not specifications for a particular product. They also leave out auxiliary consumption and changes in load. If a manufacturer already quotes usable AC energy, applying those deductions again would double-count losses.
For solar-plus-storage backup, a few other distinctions seem worth separating:
• Energy capacity (kWh) determines how much energy is available; inverter power (kW) limits the load it can supply at a given moment.
• A reserve kept for outages reduces the energy available for everyday self-consumption or peak shaving.
• Daytime PV may extend backup runtime, but its contribution depends on weather and whether the system can keep the PV operating while islanded.
• A battery connected to a grid-tied system does not, by itself, establish that the whole installation supports backup operation.
For people who have monitored real systems, which factor caused the biggest gap between estimated and actual runtime: load variation, reserve settings, auxiliary consumption, temperature, or something else? What data would you want before estimating backup duration?
Disclosure: I work with Bluesun. This is a general technical discussion; the example is not a product claim.