Hello, wanted to know if anyone knows what could've caused this?
I'm still somewhat new and not new, but we had a 3 phase motor go out for one of our trash conveyors. I work nights so everything is basically "pass it to days", but I like learning and this was low priority, so they wanted to pass it to days. I convinced my two seniors to help me take a poke at it. They're not very strong with electrical compared to me, but I'm not experienced enough to know a lot.
After we reset the overloads and turned it on, I noticed it sounded loud and rough. It only ran for 3 seconds before the overloads tripped. My seniors said it sounds like the gearbox was the issue. I wanted to test it more electrically so I clamped each phase and tested it. It took a while because it would trip after 3 seconds and it would take a couple of minutes before the overloads would take the reset.
I found phase 1 had ~3.5 amps, then I found phase 2 had ~16 amps and was surprised. Checked phase 3 and it was also ~16 amps. I immediately thought maybe this is what single phasing is (correct me if I'm wrong) but wasn't sure. I tested for voltage at the overloads and at the line side local disconnect as well. I didn't check after the disco because I felt like it would take too long so I locked out the motor and opened the peckerhead. I ohmed out all of the wires to the windings (9 lead) and they all were about 9 ohms. I figured the problem was in there somewhere causing it to single phase but we don't have a megger and that was as much as I could do. We grabbed a new motor and installed it. Turns out it was the motor having an electrical issue. Felt good knowing I figured it out and didn't do a parts cannon.
Was there anything more I could've done to trouble shoot? Was there something I did that was unnecessary? Any idea what the problem actually was? Any tips would be appreciated
Edit: also, how do you connect the leads to a dual voltage motor? I copied the last motor and wired it in wye because it was in wye. Do you measure the incoming voltage phase to phase or phase to ground and go from there? Example motor 208v-230v/460v-480v, if phase to phase is 230v, wire in Delta and if phase to phase is 480v, wire in wye?