r/RelayTechs • u/woodyever • 22h ago
Interesting Tripping event.
Had an interesting one today. Got 2 dry type 11kv transformers in a building. They are feed of the same CB on level 1. The cable goes from the CB feedera to a old school RMU in the basment with a fuse switch to TX1 then a cable up to level 8 with another fuse switch to TX2.
If we try and energise both TX's at once we go out on Earth Fault..
For saftey reasons we can only energise at the CB amd fuse switches need to be closed whilst de energised.
So we do one at a time. Yep they both hold up on their own.
Ok so heres the kicker. If we Open CB. Close TX2 fuse then close CB, energise TX2. Open CB then close TX1 fuse then Close CB we get an Earth Fault again
If we Open everything. Close TX1 fuse. CLOSE CB. Open CB. Close TX2 fuse, Close CB.... everything holds in....
Bizzare one.
Any ideas.
EF setting is 100amps via Summation. Didnt get TX sizes.