I installed a disconnect, the previous disconnect was a breaker and it had to be flipped on and of several times in order to get 240v to the contactor. I noticed that the last time I was cleaning the unit and shut off the breaker (at the disconnect) to shut power down to the outside unit.
The new AC disconnect install went smooth for the most part, the only issue I had was the 1/2 knockout in the bottom right as you can see in the pic. I had to run to the store to get a 1" to 1/2" reducing washer.
https://i.imgur.com/kbkzA9S.jpeg
When I completed connecting the wires, I turned the breaker on at the panel. 120v from L1 to ground (used the threaded mc connector for ground), 120v from L2 to ground (used the threaded mc connector for ground) and 240v when touching L1 and L2.
When testing for voltage, I also tried L1 to the box, I did not get 120v. I am almost certain I also tried L1 to the green ground screw and I did get 120v. Is the box being painted the reason I didn't get 120v during my testing? Same with L2 to the ground screw, I am almost certain I got 120v there, as well.
Normally when I'm testing from hot to the box/conduit (In Illinois many circuits are full conduit and dedicated ground wires were not ran back in the day, but I believe many electricians are now including grounds in conduit in case of conduit break, also, it might be code (now), not 100% sure on the code part.
Do I need to revisit this and make sure I get 120v when I touch L1 or L2 with one lead and the other lead on the box? I want to make sure the box is grounded.
I will go back to confirm that I get 120v from L1 to the green screw since I am not second guessing myself.
Thanks.
Update
I went back to test some more, I think the paint on the metal case is the issue.
Here is everything I tested
- L1 to L2 = 240v
- L1 to ground block = 120v
- L2 to ground block = 120v
- L1 to reducing washer = 120v
- L2 to reducing washer = 120v
- L1 to mc threads = 120v
- L2 to mc threads = 120v
- L1 to the notch on bottom of case = 120v
- L2 to the notch on bottom of case = 120v
- L1 to case = 0v
- L2 to case = 0v
The notch is where the plastic cover fits in to which covers all the wires.
I think if I buy the 1/2 ground bushing it isn't going to do anything because the case paint is still not going to give me a good reading.
For these two tests, the only thing touching the metal box is the screw that holds the block down which means the screw is getting its ground from the box, the part that is not painted. The fact that I'm getting 120v reading confirms to me that the ground on the metal case is good.
- L1 to ground block = 120v
- L2 to ground block = 120v
Does this install like fine as is or am I missing something here?
Thanks.