How do you guys traditionally size OCP on a motor with a vfd.
I tend to max it out off table 29 in the cec. Usually 250percent of fla when im doing my own stuff.
Im doing a job with an engineering firm and he is all over the place. He has a 20hp on a 50 amp breaker at 600v. The same panel has a 40 hp moter on a 40 amp breaker.
We are still at shop drawing review so I dont have the cut sheets from mechanical yet.
For those of you guys unfamiliar with 347/600 v. Rule of thumb is hp is pretty fucking close to amps.
5hp - 6.1 a
15hp-17 a
25hp-27 a
40hp-41 a
Its a rule of thumb and go off manufacturer cut sheets.
There are a few more pumps that are all over the place.
In my mind it makes sense that using a a vfd to start you wont get a huge onrush meaning you can size you breakers a bit more closely to to the fla.
Going off rule of thumb I would say that 40hp motor is slightly undersized ocp at 40.
This engineer has an ego issue and would like to avoid rfis like this.
What do you guys see in the field.
I normally see 250 percent regardless of vfd or no.