r/heatpumps • • 2h ago

Do heat pumps actually work in cold weather? Expert reveals how the technology copes at -20°C

Thumbnail
euronews.com
12 Upvotes

r/heatpumps • • 14h ago

Full Year Data - Furnace and AC vs Heat Pump by Season

Thumbnail
gallery
25 Upvotes

Hi everyone, more details in earlier posts if you are interested.

Tl/DR: 2,520 sq ft finished, 1,100 insulated, unfinished but conditioned basement. Previous 92% furnace and SEER 10 AC (both 2002 vintage) replaced with 3.5T Mitsu 42K BTU ducted w 10k aux replaced Nov 2025. With federal tax credit, CO credit and rebates, and utility rebates, installed price was 15.6K (12k in rebates and 2k fed tax credit).

I air sealed and insulated to R60 in Jul 2025, so there is a caveat comparing both seasons, but two months in 2025 summer had the same conditions as 2026. I have had 7 kW solar since summer of 2020 and the Sense meter has been handy for isolating device consumption and costs. These costs do not include the utility service fees or taxes and isolates only to the HVAC system.

I compared the previous heating and cooling seasons and normalized by heating degree days (HDD) and cooling deg days (CDD) to adjust for seasonal variability. We had a warmer winter in the Denver Metro and a hotter summer in 2026 vs 2025.

I am extremely happy with the HP and it has operated flawlessly. I wouldn't consider my bills outrageous before but they are much cheaper, especially during cooling season. I will keep tracking but this was the final analysis for the full YoY comparison.


r/heatpumps • • 9h ago

Question/Advice We are getting a furnace replaced and I'm going to push for a heat pump. Details In post

7 Upvotes

It's a forced air system with vents and we live next to the river in South bend. Our record low according to wiki is -22F. So help for models to mention is in appreciate


r/heatpumps • • 28m ago

Question/Advice Power outages ... What's the strategy?

1 Upvotes

I want to get a heat pump to replace an old oil furnace that doesn't run well. I would get new ducts at the same time. But I have one concern... Power outages.

The house is a weekend/summer home until we fix it up enough to retire there. So during the winter we won't be there to load the woodstove and prevent it from freezing if power goes out.

Anyone else here deal with something like this? The size of a standby generator to handle the heat pump load would be prohibitive (and we only have propane via rented tank, no piped gas line from the street).

I was thinking about keeping the propane for the water heater and stove, and using a tankless combi boiler with a few strategically placed radiators as a "don't freeze and please run off a smallish battery bank from EcoFlow" stopgap measure. The combi could supply hot water most of the time and turn on radiators when temp drops below some threshold.

Is there a better way to handle it when the grid goes down?


r/heatpumps • • 17h ago

40k mistake, any advice?

20 Upvotes

We recently had a new 4 ton Mitsubishi hyper heat system installed to replace our oil furnace and central air system.

I can't help but feeling I made the most expensive mistake of my life. The air handler is bolted to the basement ceiling right below my living room and it is LOUD.

The ductwork is from the 70s and lots of it is solid metal, about 1/3 has been switched out already and the noise from the ductwork is much improved, but the air handler itself is so LOUD. It's not even below freezing here but the heat kicks on in both zones and the air handler kicks up and is disruptively loud. I can't read a book peacefully on my couch anymore, or watch a show at normal volume without turning it up when the system kicks into high. Think car engine noise, but in your living room, 12+ hours a day.

It's set to the middle speed, and they did a static pressure test and got a good reading (.5, balanced between intake and output). They are warning me off turning down the air handler static pressure setting, but I'm at my wit's end and it's barely been a month. The fan of the air handler is simply ridiculous compared to the old furnace and AC and I can hear it through the living room floor.

Is there anything I can do to make life tolerable in my home again?

I am currently waiting on a quote to install vibration isolators in place of the solid metal bolts currently suspending the air handler from the joists, and I've already added rockwool insulation between the air handler and return line and the ceiling/floor above.


r/heatpumps • • 7h ago

Called about uneven heat and got told to put in a heat pump, does this add up?

1 Upvotes

Our upstairs never gets as warm as downstairs and the furnace is about 15 years old. We're near Hartford. A company came out to look and recommended a ducted heat pump with the furnace kept as backup.

His reasoning was the furnace is too big for the house, the ducts upstairs are too small, and a variable speed heat pump runs longer and evens it out.

To me that sounds like a big fix for a small problem. I figured a damper adjustment or adding a return upstairs fixes the uneven part and the furnace has years left in it. Is his recommendation reasonable for my house or is it more than I need?


r/heatpumps • • 20h ago

Question/Advice Rheem Heat Pump Water Heater

6 Upvotes

I live in the Bay Area, CA and have a Rheem heat pump water heater installed in an enclosure outside. I noticed that since the weather is cooler now, it's pretty much running 24/7. Outdoor temps are in the 50s.

I searched online and it says I can insulate the pipes. Has anyone done that and does it help?

What else can I do?

I also forgot about cleaning the air filter and will try that. Do I have to shut off the water heater to clean it? Is it fine for the HPWH to be off for a few hours for me to clean and dry the filter?

TIA

UPDATE: I took out and cleaned the air filter. It was pretty clean even though I haven't cleaned it since it was installed in March of this year.

I have the temp set to 120 degrees and it's been running on energy saver.

Energy use is:

1.7 kwh in the past 24 hours.

12.1 kwh in the past 7 days.

47.3 kwh in the past 30 days.


r/heatpumps • • 14h ago

Question/Advice California: energy incentive programs - general info and how long does the rebate take?

2 Upvotes

There are a lot of energy incentive programs across CA through the utility programs, and I'm wondering if building owners know of these services and/or have used them?

I'm not finding much online about the volume, the timelines, or how long it takes to get the incentive rebate.

In short, if you're already renovating a multifamily property and your utilities come from specific natural gas or electric companies, you can get money back on what you spend on the renovation. That applies if you do things to make it more energy efficient and meet the guidelines, such as certain kinds of insulation or more energy-efficient HVAC equipment.

-------------------------------------------------------------------------------------------------

(Why I'm asking: I'm a new energy engineer who worked for a firm that solely applied to all the different incentive programs in New York City on behalf of building owners. I'm considering a move to California, and I'm just curious about the energy landscape there. It seems like the California government and utility companies may be ahead of New York, so firms that apply to the incentives on behalf of building owners might not exist, because the government already takes care of it. Just wondering if there are firms like that in California.

To be fair, I only got through training at the firm in New York before no longer working there, so I never got to work on any real projects.)


r/heatpumps • • 13h ago

Question/Advice Heat pump/aux heat settings

0 Upvotes

We just bought an older house in the Southeast and found out it has a heat pump with auxiliary heat from electric strips. Unfortunately, the unit is 26 years old and there’s no legible labels on the outside. The previous owners left no manuals. I switched out the old thermostat to an Ecobee Premium over a month ago. I wired it correctly and runs as expected, but I’m unsure on what settings to put for the heat pump. Should I have it switch to aux heat at 30deg? When it switches, should the heat pump be completely off and using only aux heat? Or can they run together? It was cold this morning (below 30) and the aux heat was running for an extended period of time to maintain a temp of 65 which it seemed like it struggled to do. It will only be getting colder so I’d like to make sure they system is working correctly. Thanks in advance.


r/heatpumps • • 18h ago

Living with a heat pump water heater near living area

2 Upvotes

I recently bought a HPWH because my old one died and my local energy company had a $1600 credit. So it was cheaper than buying a new heat pump. I installed it myself within a couple of days in my laundry room. I knew it would be noisy and push cold air, and I don’t exactly live in a warm area. I’m in Brookings Oregon. It’s about 50 degrees most of the winter at 60-70 in the summer.

The noise has never been an issue because it’s similar to having a noisy furnace. But the cold air is getting annoying but I think I’ve got it figured out.

I keep it at about 116 degrees and run the heat pump at night. In the mornings I run it on electric only until 1pm when my wife puts my daughter down for a nap. Which is also the warmest part of the day to make the heat pump more efficient. Then at 3pm I turn it to high demand mode. It prioritizes electric and runs the heat pump for short bursts when using hot water which hasn’t been an issue. Then at bedtime. I turn it back on heat pump mode.

I’ve found that keeping the heater running constantly all day is probably for the best and just lowering it a few degrees at night. It’s not the most efficient and I would put it in the garage if I had the DIY skills but it’s working fine for now.

I know I could vent the cold air outside but I don’t want to create a vacuum in the house. And venting outside I also have to turn it around and would be able to access the main panel or the hose if it leaks.

So it’s not ideal but this is just how it works for me. Any thoughts or suggestion would be helpful.


r/heatpumps • • 1d ago

Question/Advice keeping grandma's bedroom comfortable with a mini split

Post image
5 Upvotes

my grandma's bedroom always seems to be warmer than the rest of the house once summer rolls around. the central AC doesn't seem to do a great job keeping that room comfortable.

my cozeware visio 12k mini split, it's rated at 31dB and has both heating and cooling

for those who've installed a mini split in an older house, how has it worked out? mainly wondering about noise, airflow and keeping the temperature fairly even. also how much does insulation and window type affect the sizing? don't want to end up with a unit thats too big or to small.

would appreciate any advice from folks who've dealt with a similar setup.


r/heatpumps • • 1d ago

Learning/Info One year later; replace gas furnace with heat pump in SF Bay Area

19 Upvotes

A year ago we replaced our 19-year-old Trane furnace and 30-year-old Trane A/C with a Gree Flexx Ultra heat pump (matching outdoor and indoor units). I was trying to capture a number of expiring rebates and tax credits. We still have a gas water heater.

At the time I estimated that the heat pump would be equivalent cost or maybe 10% cheaper.

The headline is that we saved about $1,000 in a $3000 total (electric+gas) bill or about -36%.

That's not the full story because of changes in rates and weather:

  1. PG&E changed their electric tariffs in March 2026 to introduce a Base Services Charge ($0.793/day) and reduced per kWh charges, especially for those of us on the EV2A tariff (for anybody with EVs or heat pumps) which dropped by about 33%. That contributed about 1/2 of the 36% savings (because the Base Services charge is new and I'm still paying for gas water heating). Gas charges are about the same year over year.

    1. I did optimize the off-peak rate by pre-heating and pre-cooling to avoid peak hours where per kWh rates are as much as 3x the off-peak rate!
  2. The weather has mostly been warmer: lower Heating Degree Days but also higher Cooling Degree Days - we've definitely run the A/C far more than 2025 (however the good news is that it's quieter and way more efficient than the Trane). I'm guessing overall we spent less.
  3. We also have solar panels, but it looks like generation was about the same between the two years.

tl;dr: After accounting for (1) PG&E tariff changes and some hand-waving on (2)&(3) we saved about $500 or 20% on our 2025 bill.


r/heatpumps • • 16h ago

Question/Advice Fujitsu Airstage Irregular Knocking

1 Upvotes

I have a Fujitsu Airstage that has been making frequent, rapid thumping noises. This occurs on about 20-50% of the time while on heating, sometimes for a minute, sometimes for 10 minutes. There’s no visible ice around. It feels like something is wrong, and my other outdoor unit does not make the same noise. Is it just the defrost cycle, or is there something wrong with the compressor?


r/heatpumps • • 1d ago

HVAC service plans in Kingman, worth paying monthly or just call when it breaks?

2 Upvotes

Retired and on a fixed income, so I'm trying to be smart about this. Our heat pump is 12 years old. 2 different companies have pitched me service plans, $15 to $25 a month, 2 tune ups a year and priority scheduling. I've also seen Semper Fi advertising one, haven't called them yet.

Part of me thinks it's just a subscription for something I'd only use twice. Part of me remembers waiting 4 days for someone in July. For people in Kingman with an older system, is an HVAC service plan worth it?


r/heatpumps • • 1d ago

Samsung 8kw, flush help

3 Upvotes

Hey all, ive got an Samsung 8KW, that i neef to flush the HEX through.

Ive got a Rothenberger Rosolar flush machine, but my pipes have a slightly smaller connection to the flow and returns on the Unit.

Is there a specific adapter i can get.

Believe the flow and returns on heat pulp are 28mm, and my pipes are 22mm connections.

Would obviously need to be female to male adapter.
Im just sure on the actual name of said adapter


r/heatpumps • • 2d ago

Heatpump Hotwater installation reviews please

Thumbnail
gallery
62 Upvotes

Live in Hamilton NZ and had this Haier unit installed, but I'm a disappointed with the position and pipe layout. If any of you have knowledge about this sort of thing, could you please post some feedback.


r/heatpumps • • 1d ago

Question/Advice Indoor unit creaking/settling

1 Upvotes

We’ve just started to turn our minisplit units back to heat, but only after dark because we have a lot of sun in the afternoon which causes our place to be sweltering. Throughout the night the unit in the bedroom is cracking, popping, snapping, it sounds like the unit housing or internal pieces are expanding and contracting. Do I have any relief in the future, is this something that eventually goes away after a few days of consistent use or am I stuck with the noise? This does not happen when it’s on fan only or on cool. Unfortunately I can’t have only fan on in the bedroom and heat downstairs because it’s a single-circuit, so I’m stuck between either a cold house or waking up through the night from the random pops.


r/heatpumps • • 1d ago

Heat pump/basement dehumidifier question

3 Upvotes

Sorry if this is a silly question to post here, but this is my first winter with a ductless heat pump system. I typically run a dehumidifier in the basement over the summer to keep things drier -- it doesn't flood or anything but I hang out my clothes rather than use a dryer so it's honestly mostly for that. In the winter with my furnace, I would turn off the dehumidifier for the season. I assumed the hot, dry air and the furnace running meant it kept things drier. Now, no more furnace. Should I run a dehumidifier in the basement all winter?

Thanks for any thoughts/guidance!


r/heatpumps • • 1d ago

Panasonic/Moveair or Mitsubishi - Hamilton Ontario

3 Upvotes

I'm replacing my 18 y/o oil furnace with a CC heatpump. The two best quotes that I've had are from the same installer and are either the Panasonic INTEROS (Moveair) 3 ton unit or the Mitsubishi Zuba. The price difference is about $3K, with the Panasonic also being an estimated $150/year less to run. It looks like warranty is the same for both.

I was going to go for the Mitsubishi, but given the specs and warranty, I'm not sure it's worth the extra 1-1/2 year payback.

I'd appreciate any thoughts/feedback if you've had experience with either/both of these.

Cheers!


r/heatpumps • • 1d ago

Bryant mini split

1 Upvotes

Hi! I’m a renter and landlord recently installed Bryant mini-splits (in Massachusetts). Ive noticed when I turn it on for hearing, my wall unit doesn‘t seem to “trigger” any air and nothing comes out. I’ve tried waiting upwards of 30 minutes, and it doesn’t seem to start blowing unless I turn up the temp up to like 71, at which point it starts blowing after a while. That doesnt really bother me, but I want to make sure it’s not a sign of a bigger issue.

Also, is it normal for it to constantly be blowing air (doesn’t seem to stop even when temp is reached)? I’ve had mitsubishi mini splits, which would periodically stop blowing air and the vanes would turn back upwards. These bryant ones seem to blow even when in the upwards position. I’m just worried it’s excessively using electricity

TIA for answers! I don’t know much about hvac 😅 Im mostly wondering if they’re all a little finicky or if I should ask for landlord to sent a tech to check it out


r/heatpumps • • 2d ago

Question/Advice Is this normal?

Thumbnail
gallery
4 Upvotes

Hi there. NZ here. Heat pump installed a few months ago. Noticed a hole in the wall poking out behind the side of the main unit and now I'm worried that our installer was a cowboy..

I want to let off a bug bomb in our roof, but I am worried about fumes pouring into our living room. Also worried about heat / moist air getting into the roof spaces through these gaps.

Pics of install attached.

The wood trim is the level of the second ceiling in the room behind the heatpump. Old house so there is a decorative lower ceiling that has been added to the bedrooms.

I think he may have mucked up and drilled the hole before checking which ceiling he was drilling into..

Pretty confident the condensate pump is tucked in this hole behind the unit.

Everything is routed up the conduit into the higher roof space. I can see a gap around this, too.

Is this normal?

I have tried contacting them about other things, but can't get hold of them.

I think the condensate pump runs for too long as I can hear sounds like someone sucking on a straw in an empty McDonalds cup.

Try again get them back or an easy DIY fix?


r/heatpumps • • 2d ago

Question/Advice Need sanity check on advice from heat pump company

5 Upvotes

My mother in law's house is about 3.5k sq feet with a larger heat pump downstairs and a smaller one in the attic for the upstairs, both installed about 3 years ago it is in a temperate climate with mild winters. Both units work fine in the summer, but there have been significant issues with the upstairs unit heating from the jump.

The initial problem was that the upstairs unit wasn't able to warm up sufficiently to actually heat the house if it was remotely cold outside and just blow cold air. The installers initial advice was to have the heater set for 75 or 78 degrees in the afternoons so that it would run and stay warm through the night, which is ridiculous because in no world does anyone want a home anywhere close to that warm.

After numerous calls to the company and visits, they ended up adding a gas line into the system to give it some extra power.

It's been working much better since, but they came in to fix something recently and are now giving my MIL some line about setting the temperature to something like 80 degrees for an hour or so in the morning to jumpstart the heat because it gives it an extra burst of power (and avoid having the heater running for 2-3 hours to get the temperature up).

I can't find anything online that suggests this is a good idea. It seems inefficient at best, and from a logical perspective it seems like having it run at that temperature when it's 55 degrees outside will give different results than when it's 40.

Is there any truth to what my MIL is being told? The more of this sort of advice we get, the more I worry that she has defective or improperly installed equipment.


r/heatpumps • • 2d ago

Question/Advice Heat sync - different room temperatures

1 Upvotes

Hi all, not sure if this is the best place to ask but we’re in a predicament with our heating system upstairs.

We have an upstairs thermostat (nest thermostat) and it’s connected to a heatsync. It provides heat to our office radiator and our bedroom radiator, and we can individually control the valves to turn them on/off if needed.

Problem is either:

  • thermostat in office, office heats up faster than bedroom because there’s a computer and maybe better insulation? This means bedroom stays cold because thermostat no longer requires heat after office reaches desired temperature (problem at night as bedroom is cold when we go to bed)
  • thermostat in bedroom, office still heats up faster than bedroom and provides heat unnecessarily. Yes I can turn the valve to switch it off manually at night once it feels warm but during the day it’s also wasted energy heating the bedroom that nobody is in. The bedroom heats up fast if the thermostat is in this room.

I’ve heard of a thermostatic radiator valve but don’t fully understand how it would work in my situation. Are there any smart devices that can help with this? We’re integrated quite nicely with Google home and home assistant but at the moment I’m manually moving thermostat to the office in the day then to the bedroom at night and I’m desperately looking for a more automatic / better solution.

Cheers!

TLDR

Can I set the office to call for heat during the day and the bedroom to call for heat before bed, while keeping the other radiator off or cooler?


r/heatpumps • • 3d ago

Question/Advice Oil Boiler Replacement Advice needed

3 Upvotes

Suffolk Long Island resident of a colonial-style two-story home , having an oil boiler for heat and water which is 28 years old. Have a 4.5-ton central air con 17+ years old with ceiling ducts. Confused if i replace the same separate units or go with a heat pump. No open issues but don’t want to wait till they break and with current oil prices things are getting worse. Need suggestions especially on the effectiveness of ceiling ducts for heat from a heat pump system and a genuine knowledgeable installer who avoids upselling