r/SubstationTechnician • • 6h ago Bravo

Update on the free substation/relay tech job board: you asked for utilities and EPS, both are on it now, plus daily job alerts by state (mods OK'd)

34 Upvotes

On 11/2 I posted relaytechjobs.com here, a free list of field testing and relay tech openings pulled every night from the testing firms' own careers pages. You gave great feedback. Here's what changed because of it:

- EPS is on it. Someone here said I forgot them. They're now one of the biggest sources on the board.

- Utilities are on it. Two of you asked. Relay, P&C and test tech openings now come from Duke, Xcel, Entergy, PG&E, Con Ed, Dominion, AEP, SRP, PacifiCorp, Constellation and more.

- It went from 302 jobs in 39 states to about 550 jobs across 43 states, from 24 employers.

- Sort by highest pay. About 220 jobs state their pay, straight from the posting. Nothing is estimated.

- Filter by date posted (last 24 hours, 7 days or 30 days), and filter to jobs that list travel.

- New: daily job alerts. Pick your states and you get one email when new jobs post there, never more than one a day. No email on days with nothing new. Unsubscribe anytime.

Alert sign-up: relaytechjobs.com/subscribe/?utm_source=reddit-substationtech

Still free, no ads, and every listing links to the employer's own application page.

Canada is still on the list for later. Which firms or utilities am I still missing?


r/SubstationTechnician • • 23h ago

Two Years Later Its Official - Mitsubishi Electric Power Products, Inc. Celebrates Opening of Advanced Switchgear Factory in Western Pennsylvania

Thumbnail
businesswire.com
16 Upvotes

Wonder who visited for a tour?


r/SubstationTechnician • • 35m ago

Just got my rank.

3 Upvotes

Went and did my test and interview over at Movalley for substation tech. Is it normal to have a small pool of applicants? Im just confused because from someone who doesnt have any experience I was ranked 10 out of 12. Im also curious on how many apprentice they let in a year?

Thank you.


r/SubstationTechnician • • 16h ago

Can an Initial Test Result Mislead You? A 220kV CVT Failure Case from China

3 Upvotes

Hi everyone!

I'm an electrical engineer at MinRong Electric, a high-voltage electrical equipment manufacturer based in China.

I spend quite a bit of time looking into high-voltage equipment failures, and one thing I've learned is that electrical faults rarely follow our first assumptions. Sometimes, the equipment seems to enjoy making engineers work overtime. 😅

Today, I'd like to share an interesting 220kV Capacitive Voltage Transformer (CVT) fault case from China in 2024.

According to research published by Kai Peng, a voltage circuit alarm occurred at an unnamed substation. Initial measurements raised suspicions about Section B of the CVT.

But here's the important part: an initial suspicion is not the same as a confirmed component failure.

The case highlights why engineers need to distinguish between three things:

1. The alarm

A voltage circuit alarm tells us something may be wrong, but it doesn't identify the exact faulty component.

2. The test results

Initial measurements can point toward a particular section, but test configuration and measurement conditions need to be considered before drawing conclusions.

3. The confirmed defect

Only after further investigation and appropriate testing can engineers determine the actual fault location and decide on corrective action.

For me, this is one of the most important lessons in high-voltage fault diagnosis: don't let the first abnormal reading make the final decision for you.

A wrong diagnosis can mean unnecessary component replacement, wasted maintenance time, and potentially overlooking the real problem.

I'm sharing this case because practical failure analysis is just as important as knowing equipment specifications.

Question for fellow electrical engineers:

When troubleshooting a CVT voltage circuit alarm, what do you usually check first: secondary wiring, test connections, capacitor-divider sections, or the electromagnetic unit?

I'd be interested to hear how other engineers approach this in the field.