I’m testing out the weather dependent mode, but mostly the rads right now. Is my flow rate and returning temp too low during the day at 7l/min?
Previous WD curve:
- Rads: 45 degrees at -3, 35 degrees at 16
- UFH: 35 degrees at -3, 27 degrees at 16
The leaving temp is 40 and returning temp (inlet plate heat exchanger) is 33. I noticed that the flow rates in the morning and afternoon is 7l/min, and the rads don’t feel particularly warm. If I turn the UFH off, the rads feel slightly warmer but the flow rates stay at 7l/min.
Yesterday, it was 21 degrees around 8am and then the heating turned off. It was set to be 22 degrees from 12:30pm-4pm so that it’s slightly warmer during peak hours (room temp is targeting 18 degrees during 4-7), but the temp went from 19.8 degrees to 20.3 degrees after the 3 hours. I target 21 degrees from 7pm to 12:30pm, and my Myson Touch has a threshold of 1 degree.
I’ve changed it to be 22 before the peak hour slots because the house was 19.5 degrees after the peak hour the day before. I just want the house to be warmer before the peak hour, and I understand that my system is just on/off for heat.
I checked the flow rates and stuff at 9pm after being out, and the house was still demanding heat, but the rads were the same. Just barely warm, and temp was 19.8 when I got back.
Since it was 48-60 hours since I changed to WD mode, I changed it again last night:
- Rads: 45 degrees at 0, 35 degrees at 16
After the system restart, the flow rate changed to 15l/min and then it heated up the house within an hour. The LWT was 43 and returning temp was 40.
This morning, it's somewhat the same with the returning temp. The LWT is 44 and returning temp is 33-34, and flow rate is 7l/min. It's been demanding heat since 6am and the house is 20.3 degrees.
I don't know the exacts but 7l/min seems to be the lowest that it runs. There's no error messages. I cannot change the delta T for the rads even if I change it to fan coil since it's an additional zone, and it's always locked to 12 degrees. Delta T for UFH is 5 degrees.
I don't have battery or solar. I'm on the Eon heat pump tariff.