Background in my earlier post if anyone wants it — same house, deep retrofit, 1930s semi: https://www.reddit.com/r/ukheatpumps/comments/1xqy06q/
Following on from that post about being quoted 10kW against a 4kW load — both installers have now landed on 8kW and I've got two full proposals.
Installer A — Ideal HP290 8kW
- 7.99 kW output at design conditions
- 40°C design flow temp, SCOP 4.56
- Upstairs: 6 radiators + 3 dual-fuel towel rails, sized 3–14% above room load
- 279L Ideal cylinder
- MCS020 noise calc provided: 27dB, pass
- Room-by-room heat loss provided
- Electrician not clearly included
- £17,800 after BUS grant
Installer B — Viessmann Vitocal 150-A 8kW
- Output at design conditions not stated
- Design flow temp not stated, SCOP not stated
- Upstairs: 6 Type 22 (K2) + 3 towel rails, 700–2100mm, very generous
- OSO Delta Geocoil cylinder
- No MCS020 noise calc
- No room-by-room heat loss
- Electrician included
- £24,212 after BUS grant
B also offered UFH on every floor for £31,178 after grant, which I've parked.
The actual difference is the emitters, not the heat pump.
A has sized every radiator to 3–14% above its room load at 40°C flow. Run that system at 35°C and seven of the eight rooms fall short. So it's committed to 40°C for the life of the radiators.
B's radiators are big enough that they'd deliver the same room loads at roughly 30–35°C. He hasn't actually stated a design flow temperature, which is a gap I need to close, but the emitter sizes imply it.
So £6,400 buys: maybe £900 of energy over 20 years if I ever ran it at 35°C, a Viessmann instead of an Ideal, an electrician worth maybe £1,200, and emitter headroom I might never use.
Where I'm stuck
I asked A why not 35°C and the answer was better than I expected: the bathrooms are the binding constraint (22°C rooms lose ~40% of emitter output going 40→35°C, and towel rails are weak anyway), and more importantly I'm designing against a house that doesn't exist yet. My wall build-ups aren't confirmed by the builder and I haven't done an airtightness test. A 40°C design can be pushed to 45°C if the fabric underperforms. A 35°C design with 3% margins has nowhere to go.
That seems like a fair point and not just an excuse, but I'd like a sanity check on it.
Questions
- Is 3–14% emitter margin at 40°C enough, or is that the thing people regret? Anyone living with a system sized that tight?
- Is the headroom to drop to 35°C later worth real money, or is it a thing people talk about and never do?
- Ideal HP290 vs Viessmann Vitocal 150-A — any strong views? Couldn't find a published minimum modulation figure for either.
Not naming either of them.