r/ukheatpumps • • 5h ago

Vaillant aroTHERM Pro 7kW vs Plus 5kW – which would you choose for a 6.4kW heat loss?

6 Upvotes

I've recently had a survey completed and I'm trying to decide between two heat pumps.

Property and heat loss:

  • Floor area: 91.46m²
  • Calculated heat loss: 6.4kW
  • Design outside temperature: -3.6°C
  • Target indoor temperature: 21°C
  • Ventilation heat loss: 2.46kW
  • Estimated annual space heating demand: 15,150kWh

Heat pump options:

  • Vaillant aroTHERM Pro 7kW – guaranteed efficiency of 340–375%.
  • Vaillant aroTHERM Plus 5kW (anthracite) – guaranteed efficiency of 345–380%.

I'm leaning towards the 5kW Plus because of its lower minimum modulation, quieter operation and slightly better predicted efficiency. However, I'm concerned about whether it has enough capacity on the coldest days.

I'm also planning some improvements to the property:

  • Increasing loft insulation from approximately 100mm to 300mm.
  • Draught-proofing windows, doors and other gaps.
  • Installing thermal curtains.

The upstairs ceilings currently account for 342W of the calculated heat loss, and ventilation accounts for around 38% of the total.

My thinking is that there are some simple improvements to improve my heatloss and I don't want to end up with an oversized heat pump for the next 15–20 years.

My questions are:

  • Would you be comfortable installing the 5kW Plus with this heat loss?
  • What is the real-world output of the 5kW Plus in sub-zero temperatures?
  • Would the 7kW Pro be oversized if I did some simple improvements e.g. extra loft insulation, plugging gaps etc.
  • How much weight would you give to the lower minimum modulation of the Plus?

r/ukheatpumps • • 18h ago

Help/Advice Weather dependent mode flow rates and such

5 Upvotes

I’m testing out the weather dependent mode, but mostly the rads right now. Is my flow rate and returning temp too low during the day at 7l/min?

Previous WD curve:

  • Rads: 45 degrees at -3, 35 degrees at 16
  • UFH: 35 degrees at -3, 27 degrees at 16

The leaving temp is 40 and returning temp (inlet plate heat exchanger) is 33. I noticed that the flow rates in the morning and afternoon is 7l/min, and the rads don’t feel particularly warm. If I turn the UFH off, the rads feel slightly warmer but the flow rates stay at 7l/min.

Yesterday, it was 21 degrees around 8am and then the heating turned off. It was set to be 22 degrees from 12:30pm-4pm so that it’s slightly warmer during peak hours (room temp is targeting 18 degrees during 4-7), but the temp went from 19.8 degrees to 20.3 degrees after the 3 hours. I target 21 degrees from 7pm to 12:30pm, and my Myson Touch has a threshold of 1 degree.

I’ve changed it to be 22 before the peak hour slots because the house was 19.5 degrees after the peak hour the day before. I just want the house to be warmer before the peak hour, and I understand that my system is just on/off for heat.

I checked the flow rates and stuff at 9pm after being out, and the house was still demanding heat, but the rads were the same. Just barely warm, and temp was 19.8 when I got back.

Since it was 48-60 hours since I changed to WD mode, I changed it again last night:

  • Rads: 45 degrees at 0, 35 degrees at 16

After the system restart, the flow rate changed to 15l/min and then it heated up the house within an hour. The LWT was 43 and returning temp was 40.

This morning, it's somewhat the same with the returning temp. The LWT is 44 and returning temp is 33-34, and flow rate is 7l/min. It's been demanding heat since 6am and the house is 20.3 degrees.

I don't know the exacts but 7l/min seems to be the lowest that it runs. There's no error messages. I cannot change the delta T for the rads even if I change it to fan coil since it's an additional zone, and it's always locked to 12 degrees. Delta T for UFH is 5 degrees.

I don't have battery or solar. I'm on the Eon heat pump tariff.


r/ukheatpumps • • 9h ago

Anyone used Heatable for a heat pump with Adia Thermal?

4 Upvotes

I’m renovating near Chelmsford and Heatable reckon they can do a 10 kW Vaillant and a 300 litre cylinder for about £8,800 after the grant. Seems pretty reasonable for a big national installer. They’ve told me Adia Thermal is included.

Has anyone had Heatable fit theirs? How was the install, and were they any good at sorting things out afterwards?

The bit I’m unsure about is Adia. I get that it’s meant to balance the radiators automatically, but does that mean the installer leaves more of the setup for Adia to sort out after they’ve gone? We’ll have new radiators and underfloor heating. What actually gets checked before they leave, and how has it been to run through winter?

Quick quote sense check

Sorry for including solar too. I figured quite a few people here have both, and I’d like one company to do both jobs. Heating prices are after the grant and include underfloor heating and radiator fitting. No one’s priced the radiators themselves yet.

  • Heatable (£47k total) · £25.9k heating + £21.1k solar, with 19 panels, an 18 kWh battery and whole-home backup.
  • Better Planet (£54.1k total) · £28.5k heating + £25.6k solar, with 18 panels, an 18 kWh battery and whole-home backup.
  • JMR Heating & Energy (about £43k total) · £22.1k heating + about £20.8k for a similar solar and battery setup with backup.

I’m leaning towards Better Planet because they’ve done more work on the heating design so far, but £7k more than Heatable is a fair chunk. Does anything jump out at you?


r/ukheatpumps • • 7h ago

Help/Advice Installer recommendations - Cambridgeshire

3 Upvotes

Hi, I'm looking for recommendations for heat pump installers that cover Cambridgeshire and can install a system with ducted fan coil units upstairs (FCUs in the loft) and wall mounted FCUs downstairs. I've been eyeing up the Panasonic Aquarea system with their hydronic FCUs but I'm open to other options. I found a couple of potential companies but one of them will only do installs whilst the house is being built and the other isn't MCS certified so they can't do the BUS grant. Bonus points if the installer can also install solar panels and a Fogstar battery + inverter system.


r/ukheatpumps • • 11h ago

Switch from System boiler worth it

3 Upvotes

Hi, Wondering if I should switch out system boiler with ASHP or keep the old setup and spend the money on all year round AC-heating/cooling

Old Victorian property over 3 floors. Would say we are high usage household due to WFH, plenty showers etc

If went down the AC route, I would do the majority of heating via AC and use the old boiler for heating the water mainly.

Looking for peoples thoughts on this or help question the possibilities as I'm completely new to all this.


r/ukheatpumps • • 20h ago

Help/Advice Mitsubishi Ecodan Tips/Advice

3 Upvotes

All I am looking for is tips or advice on the system I have installed at my property. I have been tinkering now for a while and think I have the best setup I can get with what I have. The energy and heating system i have is:

- 12kw R290 Ecodan
- 250l tank
- 30 Aiko Gen 3 540w Solar Panels
- 2xBAT 10 Sigenstor batteries
- 10kw inverter

I have lowered flow temp max to 43 degrees Celsius and the heat pump will run at 1.1kw-2.0kw while maintaining temp at 20 degrees. At this max flow temp the house will heat by about 0.1-0.2 degrees per hour but the system usually runs at between 33-38 degrees when maintaining temperature.

On cold grey days like we have just had, I’m in between Sheffield and Lincoln so it has been around freezing for most of the day recently, we just have enough battery to last the day with some solar which I’m happy with. The heat pump used 20kwh max on the coldest day and that included a legionnaires cycle.

I pair this with a TOU tariff that I use mainly for charging my car but also charging the home batteries. During this time I have the heating on from 2am-5am to raise temp to 21 degrees and then at 6am when that low cost energy finishes I drop temp to 21 degrees. This then means the heat pump turns off for about 2-3 hours by which point I start to get some solar.

I feel i have it as good/efficient as I can get it. I do need to replace some single panel radiators with K2/type22 which would improve efficiency further but at the moment that cost can wait.

Any tips or advice is welcome.

Cheers.


r/ukheatpumps • • 4h ago

Constant fault in Grant Aerona A2W heat pump

Thumbnail
gallery
2 Upvotes

Hey All,

I am having issues with my grant aerona air to water heat pump, model HPID6R32.

We recently had a power flush done and a service done, and I am getting an FU alarm and some times P1 alarm.

See 4 images attached.

Image-1: over view of the hotpress room

Image-2: bleed point(red) and bypass valve setting (purple)

Image-3: Mag filter after 2 weeks of power flush.

Image-4: Fu alarm code

If you see image-2, I constantly find small airpockets at those bleed point, they directly on path of demand hot water inlet and outlet.

I get the FU alarm every 18-26 hrs and p1 alarm every 2-3 days.

I have tried the following:

  1. Clean mag filter
  2. Keep bleeding air as shown in image-2z
  3. Set Bypass valve to lowest setting of 0.1

Can any one please help me out.


r/ukheatpumps • • 8h ago

Buying a 3 bedroom 1950 cavity semi - looking at a new system.

2 Upvotes

We're in the late process of buying a 3 bedroom house. The loft has been coverted.

Current system is a gas boiler & Unvented water cylinder.

Is it worth installing Solar panels, battery and heat pump? We'll have approximately £15k left over from the house sale & purchase.

Given the rising energy costs. We're planning on getting rid of the gas to the house (new induction hob ect)


r/ukheatpumps • • 10h ago

More on Stiebel HP - Interesting watch!

Thumbnail
youtu.be
0 Upvotes