I am going to be cleaning/repairing my pressure reducing valve (PRV)and replacing my thermal expansion tank (TET) what is the correct order of operation? My understanding is that I should get the pressure reducing valve taken care of, get it set where it needs to be, adjust the new Thermal expansion tank to match the pressure I set and then install it. Or should I get the TET replaced now?
My PRV (Zurn NR3XL) is having issues. The pressure will initially be at about 60psi then slowly creep up to about 70psi. Then if I run a faucet it drops to about 40psi before slowly climbing back up to 70psi. I have a repair kit in the mail, just in case when I open it up there is a damaged part that needs replacing, I was stoked to learn there is a cleaning/repair options and I don't need to replace the whole thing. My TET also seems shot, when I checked it it seemed to have no pressure in it and if I tried to add pressure it would not take any until I managed to get the PSI on the pump over 100psi. There was pop and a drop at the pump and I could then pump air into it.
*Update 11-21-2026
This morning I turned off the line into the water heater to see what the line pressure would do. while running the pressure drops to 40psi. when it is off it jumps to 80psi. The same behavior is observed with the line to the hot water being on. The repair kit for the PRV will not arrive until 11-30, and I would prefer to wait until that arrives to clean the internals of it in case something does need to be replaces. I also removed the TET and confirmed it is shot. detached it would not hold air, just vented out of the opening for the water, and it had some nice brown water sitting in it.
What I decided to do is, with a tap running I adjusted the PRV to set a dynamic/flowing pressure of 60psi. I then decided to set the new TET between the dynamic and static pressure (70psi). Please feel free to yell at me if this is a boneheaded idea and correct what I should do. After attaching the new TET the pressure fluctuation are the same, 60psi dynamic and about 80psi static. Once I get the repair kit I will address the PRV, depressurize the water heater, and readjust the TET.